Factory settings
B.1 Transmitter factory settings
MAG 6000 I / MAG 6000 I Ex de transmitter
90 Operating Instructions, 04/2016, A5E02083319-AG
Batch
Off
Batch
(Page 79)
•
Batch quantity
0
Sensor size dependent
•
Batch compen-
sation
0
-100 ... +100 m
3
•
Batch counter
Down
Up, down
500 Hz, 1 kHz, 5 kHz, 10 kHz
Digital
output -
frequency
•
Time constant
5 s
0.1 ... 30 s
Digital out-
put - pulse
(Page 77)
•
Pulse polarity
Positive
Positive, negative
•
Pulse width
66 ms
64 μs 130 μs, 260 μs, 510 μs, 1.0 ms, 2.0 ms, 4.1 ms,
8.2 ms, 16 ms, 33, ms, 66 ms, 130 ms, 260 ms,
520 ms, 1.0 s, 2.1 s, 4.2 s
•
Volume/pulse
Sensor size
Dimension-dependent
•
Time constant
0.1 s
0.1 ... 30 s
External input Off
Batch, reset totalizer, freeze output, forced output,
off
External
input
(Page 80)
•
Batch
Start
Start, hold/continue, stop, Qmax 2
Sensor
characteris-
tics
Correction factor 1 0.85 ... 2.00
Language English English, German, French, Danish, Swedish, Finnish,
Spanish, Russian, Italian, Portuguese, Polish
Changing
language
Primary field Flow rate Flow rate, Totalizer 1, Totalizer 2 Changing
operator
menu setup
(Page 45)
Title/subtitle lines Flow rate Flow rate, Flow velocity, Qmax, Totalizer 1,
Totalizer 2, Totalizer 1 reset, Totalizer 2 reset,
Batch start/paused/stop, Batch cycle counter,
Batch cycle counter reset, Sensor size, Sensor
type, Error pending, Status log, Tag No.