8 TECHNICAL DATA
110
SITRANS FX330
www.siemens.com/flow 08/2022 - A5E36751269-AG EN
Foundation Fieldbus
Description Galvanically isolated according to IEC 61158-2
Current consumption: 16
mA
Permissible bus voltage: 9…32 V; intrinsically safe: 9...24 V
Bus interface with integrated reverse polarity protection
Link Master function (LM) supported
Tested with Interoperable Test Kit (ITK) version 6.1
Function blocks 5 x analog input (AI), 2 x Integrator (IT), 1 x PID, 1 x analog output (AO)
Output data Volume flow, mass flow, norm. volume flow, corrected volume flow, temperature 1,
temperature 2, pressure, density, velocity, gross power, net power, FAD, vortex
frequency, Reynolds number, specific heat capacity, specific enthalpy, sensor
electronics temperature, converter electronics temperature, diagnostic data
Approvals and certificates
Declaration of conformity This device fulfils the statutory requirements of the relevant directives and regulations.
The manufacturer certifies successful testing of the product by applying the conformity
mark on the device.
For further information on directives, regulations, standards and certifications, please
refer to the declaration of conformity.
Standard version Non-Ex
Functional safety according to
IEC
61508
Depends on I/O variant and flow sensor. For detailed information refer to the "Safety
manual".
Hazardous areas
ATEX / UKEx ATEX II2 G - Ex ia IIC T6...T2 Gb
ATEX II2 G - Ex d ia IIC T6...T2 Gb (not for signal converter in stainless steel housing)
ATEX II3 G - Ex nA IIC T6...T2 Gc (not for signal converter in stainless steel housing)
ATEX II2 D - Ex tb IIIC T70 Db (not for signal converter in stainless steel housing)
IECEx IECEx - Ex ia IIC T6...T2 Gb
IECEx - Ex d ia IIC T6...T2 Gb (not for signal converter in stainless steel housing)
IECEx - Ex nA IIC T6...T2 Gc (not for signal converter in stainless steel housing)
IECEx - Ex tb IIIC T70°C Db (not for signal converter in stainless steel housing)
QPS (USA & Canada) QPS IS Class I Div 1
QPS XP Class I Div 1 (not for signal converter in stainless steel housing)
QPS NI Class I Div 2 (not for signal converter in stainless steel housing)
QPS DIP Class II, III Div 1 (not for signal converter in stainless steel housing)
Other standards and approvals
QPS (USA & Canada) QPS Ordinary Locations
NAMUR NE 06, NE 21, NE 23, NE 32, NE 43, NE 53, NE 107
Further approvals on request.