OPERATION 6
83
SITRANS FX330
www.siemens.com/flow08/2022 - A5E36751269-AG EN
C2.1.6 Error Function This function triggers a current output signal in case of an error detection with status
type F (for details refer to
Status messages and diagnostic information
on page 92).
Select:
- Off: No error current signal is sent.
- High: Error current signal as defined in C2.1.7 is sent.
- Low: Error current signal as defined in C2.1.8 is sent.
- Hold: Last current value is held.
C2.1.7 Low Error Current Enter: 3.5...3.6 mA, available if "Error Function = Low"
C2.1.8 High Error Current Enter: 21...21.5 mA, available if "Error Function = High"
C2.1.9 Trimming This function enables to trim the current output.
Trimming is started by entering the menu.
C2.1.9.2 4mA Trimming Trimming of 4 mA point.
Enter measured value for 4 mA point. Reset to 4 mA restores the factory calibration.
C2.1.9.5 20mA Trimming Trimming of 20 mA point.
Enter measured value for 20 mA point. Reset to 20 mA restores the factory calibration.
C2.2 Binary Output For possible functions of the binary output refer to
Binary output
on page 46
C2.2.1 Function Select: Off / Pulse / Frequency / Status / Limit Switch
Unless otherwise ordered the binary output is inactive.
C2.2.2 Pulse Output Only available if "Pulse" is selected in C2.2.1.
C2.2.2.1 Measurement Select: Volume Flow / Mass Flow / Norm. Volume Flow / Gross Power /
Net Power
Gross/net power is just available for non-standard meter types measuring steam or
water.
Availability of selection depending on meter type and medium configuration.
C2.2.2.2 Value p. Pulse Define value per pulse in unit according to measurement variable selection.
C2.2.2.3 Pulse Width Define pulse width in ms.
C2.2.2.4 100% Pulse Rate Define 100% pulse rate in Hz.
C2.2.3 Frequency Output Only available, if "Frequency" is selected in C2.2.1.
C2.2.3.1 Frequency Out.
Meas.
Select: Volume Flow / Norm. Volume Flow / Mass Flow / Density / Temperature1 /
Temperature2 / Pressure / Vortex Frequency / Velocity / Specific Enthalpy / Specific
Heat Capacity / Reynolds Number / FAD / Net Power / Gross Power
Availability of selection depending on meter type and medium configuration.
C2.2.3.2 Pulse Shape Select: Automatic (constant pulse width based on pulse/pause ratio = 1 at max. pulse
rate)
/ Symmetric (pulse/pause ratio = 1) / Fixed (Fixed pulse length; set pulse width in
C2.2.3.3)
C2.2.3.3 Pulse Width Only available, if "Pulse Shape = Fixed" is selected in C2.2.3.2.
Enter pulse width in ms.
C2.2.3.4 0% Pulse Rate Enter value for 0% pulse rate in Hz.
C2.2.3.5 100% Pulse Rate Enter value for 100% pulse rate in Hz.
C2.2.3.6 0% Range Enter value for 0% range in unit according to measurement variable selection.
C2.2.3.7 100% Range Enter value for 100% range in unit according to measurement variable selection.
C2.2.4 Status Output Only available, if "Status" is selected in C2.2.1.
Function Setting / Description
C2 Output