TS100/TS200/TS300/TS500/TSinsert/TSthermowell
Compact Operating Instructions, 01/2018, A5E03920348-AE
41
Service and maintenance
7
WARNING
Impermissible repair of explosion protected devices
Risk of explosion in hazardous areas
Repair must be carried out by Siemens authorized personnel only.
WARNING
Humid environment
Risk of electric shock.
Avoid working on the device when it is energized.
If working on an energized device is necessary, ensure that the environment is dry.
Make sure when carrying out cleaning and maintenance work that no moisture
penetrates the inside of the device.
Recalibration
Temperature sensors are essentially maintenance-free. However, we recommend
recalibration under the following conditions:
Processes with strong vibrations or changes in temperature.
Food, pharma, biotechnology applications (annually), TS300 only.
Processes that demand high measuring accuracy and safety.
Note
Recalibration intervals
Define the recalibration intervals for the specific process or plant. With constant operating
temperatures and a low load, the reference values are as fo
llows:
< 2 years at temperatures up to 400 °C
< 5 years at temperatures up to 200 °C

Table of Contents

Other manuals for Siemens SITRANS TSinsert

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SITRANS TSinsert and is the answer not in the manual?

Siemens SITRANS TSinsert Specifications

General IconGeneral
BrandSiemens
ModelSITRANS TSinsert
CategoryTemperature Controller
LanguageEnglish

Related product manuals