e1973c-5
02.2004
29
Fire & Security Products
Siemens Building Technologies Group
Disabling the remote fault transmission facility
1. Press
St
.
Display shows
2. Select option 2. 2. 4.
Display shows
for a few seconds
The remote fault transmission is disabled.
The yellow LED of the display field Isolation is on.
The text display indicates that no alarm message is pending.
Enabling the remote fault transmission facility
1. Press
St
.
Display shows
2. Select option 1. 2. 4.
Display shows
for a few seconds
The remote fault transmission is enabled.
The yellow LED of the display filed Isolation is off, if no other parts of the system are isola-
ted.
SELECT: 1. ENabling
(main menu) 2. DISabling
3. INFO polling
4. other functions
RT−fault DISABLED
timeout /hm: menu Stop: end operating
SELECT: 1. ENabling
(main menu) 2. DISabling
3. INFO polling
4. other functions
RT−alarm ENABLED
timeout /hm: menu Stop: end operating