Fire & Security Products
Siemens Building Technologies Group
Test of Remote Transmission (RT)
Purpose and principle
In test mode the function of the remote transmission can be tested without activating an alarm
device or a manual call point.
The function of the remote transmission facility has to be checked periodically. The remote alarm
transmission and the remote fault transmission can be tested separately.
Frequency
The acoustic alarm devices have to be tested at least once a year.
i
Before the remote alarm transmission is tested, inform the fire brigade!
Test procedure for remote alarm transmission
1. Inform the fire brigade before a remote alarm transmission test will be performed.
2. Press
St
.
Display shows
3. Select option 4. 2. 1. 3.
To initiate the remote ALARM test.
Display shows
4. If the fire brigade is informed, press
ok
.
Display shows
The test runs for 30 sec. The remaining
time is indicated.
After the test has finished, the submenu is displayed again.
If the remote alarm did not arrive at the fire departement, call the SIEMENS service organization
for repair.
"
The test can be stopped before expiration of the 30 seconds by pressing
hm
.
Test procedure for remote fault transmission
1. Press
St
.
Display shows
2. Select option 4. 2. 1. 4.
To initiate the remote FAULT test.
Display shows
The test runs for 30 sec. The remaining
time is indicated.
After the test has finished, the submenu is displayed again.
If the fault message did not arrive at the remote location, call the SIEMENS service organization
for repair.
"
The test can be stopped before expiration of the 30 seconds by pressing
hm
.
SELECT: 1. ENabling
(main menu) 2. DISabling
3. INFO polling
4. other functions
ATTENTION: testing remote transm. ALARM!
>> fire brigade notified? > then: ok
hm: back to menu Stop: end operating
TESTING remote transm. ALARM (RT−alarm):
> remaining active time
hm: stop test Stop: end operating
SELECT: 1. ENabling
(main menu) 2. DISabling
3. INFO polling
4. other functions
TESTING remote transm. FAULT (RT−fault):
> remaining active time
hm: stop test Stop: end operating