Operating access
Possible access levels
Three main access levels are defined allowing different privileges for the operation of the fire
detection system. Access is provided by a four digit password for the higher access levels, re-
spectively.
i
After 3 consecutive incorrect password entries the operation access is disabled for 15 minu-
tes.
Overview of the access levels
Access level
Group of persons Enabled operating functions
Access level 1
(no password)
everybody − Scrolling alarm messages
− Acknowledge messages
Access level 2
(password required or
key−lock switch, if instal-
led)
system operator 1 (e. g. jani-
tor)
− Acknowledge messages
− Alarm reset
− Fault/Info scrolling
− Isolation of system parts
− Poll system information
− Perform system tests
Access level 3
(various passwords to di-
stinguish)
service engineer
or
system operator 2 (e. g. se-
curity officer)
− Edit user text
service engineer − Service functions
− Erase data
service engineer − Application setting
− Setting passwords
Automatic timeout
The access by password is automatically cancelled if no key is operated for:
5 min during state of “normal operation“
30 sec during condition “alarm“
How do I get operating access?
"
Enter the password on the keypad as described below.
or
"
Turn the keylock switch in horizontal position.
Access with level user operating 2 is provided as long as the key is left in horizontal position.
System on
Fault
Isolation
Detector
test mode
FC330A
Remote alarm
fault / off
Alarm horn
fault / off
System fault
Remote alarm
active
Alarm delay
off
Premises
manned
hm
0
del
789
456
12
3
F1
F2
ok
Start/
Stop
1
2
Acknowledge messages
possible:
with access level 1 p
with access level 2 p