Fire & Security Products
Siemens Building Technologies Group
Poll system status
Purpose
After acknowledging messages from various system states differing from “normal operation” as
“isolation” or “fault”, detailed information may be no longer visible on the text display. Only the
LEDs of the display fields and a more general message like “parts of the system isolated” on the
text display indicate a special system state. More detailed informations e. g. which zones are
isolated, or which elements are faulty can be retrieved by polling the system status at any time.
Polling the system status
1. Press
St
.
Display shows
2. Select option 3. 1.
Display shows
3. Select option 1.
A scroll page for the selected item is dis-
played, here for example for “fault“.
Display shows
4. Use and to scroll through the
messages.
Display shows
5. Use
hm
to go back to the submenu or
St
to terminate the system status polling.
SELECT: 1. ENabling
(main menu) 2. DISabling
3. INFO polling
4. other functions
STATUS: 1. fault
(3.1) 2. isolation
3. pre−alarm
4. techn.alarm /element status
display FAULT messages: total:##
(key: ↓ = forward / ↑ = backward)
hm: back to menu Stop: end operating
display FAULT messages: total:##
fault messages..............
↓: forward ↑: backwards