Lamp test
Purpose of the lamp test
Alarms, faults and operating state of the fire detection system are indicated by LEDs in the dis-
play fields, the text display and the alarm buzzer of the control console.
To check the correct function of these parts the lamp test can be initiated: All visual and audible
devices of the control console are activated for a few seconds.
Frequency
The lamps have to be tested at least once a year.
Lamp test procedure
1. Press
St
.
Display shows
2. Select option 4. 2. 2. 1.
To initiate the lamp test.
Display shows
3. Check:
all LEDs on?
buzzer audible?
missing segments in text display?
If one or more devices are malfunctional, call the SIEMENS service organization.
i
Lamp test on local indication and control panels page 5.