e1973c-8
02.2004
35
Fire & Security Products
Siemens Building Technologies Group
4. After entering the last number press
ok
twice.
Display shows
for a few seconds
The selected detector zones are set
into detector test mode.
Display shows
The yellow LED of the display field de-
tector test mode are on.
Setting a zone range or all detectors into detector test mode
1. Press
St
.
Display shows
2. Select option 4. 2. 3. 2.
Display shows
3. Enter the first number of the desired
zone range (e. g. 2) or 555 for testing
all zones.
Display shows
for a few seconds
4. Enter the last number of the desired
zone range (e. g. 5).
Display shows
The selected zone range is set into de-
tector test mode.
Display shows
Terminating the detector test mode for single zones
1. Press
St
.
Display shows
2. Select option 4. 2. 3. 1.
Display shows
3. Press
del
to delete all displayed zone
numbers and enter “0” (zero) instead.
4. Press
ok
twice.
Display shows
for a few seconds
The detector test mode is terminated for
all detector zones.
Terminating the detector test mode for a zone range
1. Press
St
.
Display shows
2. Select option 4. 2. 3. 2.
Display shows
3. Enter “0” (zero) and press
ok
.
Display shows
for a few seconds
The detector test mode is terminated for
all detector zones.
Mode ’DET. TEST’ zones: ###,###,###,###
Outputs NOT activated
timeout /hm: menu Stop: end operating
Mode ’DET. TEST’ zones: ###,###,###,###
Mode ’DET. TEST’ range: ### − ###
TUE 27.7.99 10:35
SELECT: 1. ENabling
(main menu) 2. DISabling
3. INFO polling
4. other functions
No ’DET.TEST’ mode, set range ### − ###:
> zone no.? (555=all, 0=end)
zone range ### − ### in ’DET. TEST’ mode
Outputs NOT activated
timeout /hm: menu Stop: end operating
zone ### SELECTED. ok = SINGLE zone
> 2nd zone no.? (range ### − ###)
Mode ’DET. TEST’ zones: ###,###,###,###
Mode ’DET. TEST’ range: ### − ###
TUE 27.7.99 10:35
SELECT: 1. ENabling
(main menu) 2. DISabling
3. INFO polling
4. other functions
No ’DET. TEST’ mode, set single zone(s):
> zone no.? (max. 4)
hm: back to menu Stop: end operating
’DET. TEST’ mode TERMINATED
timeout /hm: menu Stop: end operating
SELECT: 1. ENabling
(main menu) 2. DISabling
3. INFO polling
4. other functions
No ’DET.TEST’ mode, set range ### − ###:
> zone no.? (555=all, 0=end)
hm: back to menu Stop: end operating
’DET. TEST’ mode TERMINATED
timeout /hm: menu Stop: end operating