SDS Series
16
WIRING CONNECTIONS TO CONTROLLER:
Install the controllers VDC power supply in close proximity to the controller.
The controller is supplied with quick disconnect terminal strips. It may be conven-
ient to unplug the terminal strips to terminate the wiring, they can then be
plugged back into their headers on the PCB motherboard.
Connect the 36VDC RED / BLACK power leads to the R and B terminals at the con-
troller.
Sensor cables should be not greater than .2mm² (AWG24) when directly wiring
into the controller terminal strip. The Two-wire terminals [O/P] are connected to
the SD-SP filter/protection device. See next section Lightning Protection
Connect the PumpNodeRED wires to the two-wire cable, BROWN wires to the
pump start relay. Ensure the pump start relay is a low current rated device at
maximum 24VAC 65mA (Omron LY 24VAC series)
When installing a direct relay module SD-1-DR (RelayCube) it will require a sepa-
rate 24VAC power supply. Please ensure this is rated a minimum of 1 amp.
The RelayCubecan be mounted anywhere that is convenient along the two-wire
cable provided a 24VAC power source is available.
Do not earth the 24 VAC at the RelayCube™. See page 15.
OPERATIONAL AND ENVIRONMENTAL REQUIREMENTS:
Ambient operating Temperature 0 to 55 degrees centigrade maximum.
Main supply voltage for controller power supply 100240 VAC 50/60Hz
Ensure adequate air ventilation to assist cooling if installed in cubicle.
Power supply must be installed by a qualified electrical technician.
Use only the power supply supplied with the controller or a recommended alterna-
tive by Signal Data Systems.
Position the controller away from direct sunlight and water spray.
Avoid close proximity to possible electromagnetic interference and particularly
close proximity to VSD devices unless they meet all the manufactures installation
requirements. Signal Data Systems recommend a distance of 5 meters from
possible sources of electromagnetic interference.
MOUNTING CONTROLLER:
Locate at an easy viewable eye level with a minimum top clearance of 200mm
for lid to be fully opened.
Allow sufficient space at the bottom of the controller for conduits and cable.
Some installations may require a separate terminal strip mounted in close proximi-
ty to the controller if large gauge two-wire cable is used.
Mount the controller using all four mounting points on a flat level surface.
Installation