SDS Series
17
Installation
TWO-WIRE CABLE REQUIREMENTS:
Signal twisted pair cable with tinned copper conductors certified for direct burial
is recommended for optimum performance.
Signal recommends all two-wire cable joints should be soldered in a professional
manner for maximum reliability. If not soldered, they must be tightly twisted to-
gether for a minimum distance of 30mm then clinched over. It is the installers
responsibility to provide low resistance water tight cable joints.
Waterproof connectors must be certified for below ground use. Direct bury con-
nectors are not suitable for permanent submersion in water unless specifically
rated. Long periods of full emersion will cause connector failure.
Great care should be taken to ensure the cable insulation is not compromised, i.e.
nicks in the inner cable insulation etc. It is the installers responsibility to en-
sure there is no electrical leakage to earth in the cable network.
Ensure the two-wire cable is well distanced from high voltage cables. If the cable
crosses a high voltage line it must be at right angles with a minimum clearance of
600mm.
Never install the two-wire cable in the same conduit or strapped to any electrical
high voltage cable.
LIGHTNING PROTECTION:
For lightning protection to be effective the energy of the strike needs to be in-
stantly gated to earth.
Connect the ORANGE wires from the SD-SP surge arrester to the O/P terminals at
the controller.
For best results flat braided cable is used to connect to an earth stake of at least 2
metre length with a resistance to earth of 10 Ohms or less. Locate the SD-SP as
close as possible to the earthing stake.
For additional protection, install SD-SA filter/arrestors every 300 meters or every
16 valves. Connect to an earth stake with a resistance of 10 Ohms or less to
earth.
Note: A 10 Ohm or less resistance to earth can be difficult to achieve in sandy soils. To re-
duce the damaging effects of lightning follow these three rules:
1. Ensure that no bare cable conductors are in contact with the soil.
2. Use only approved direct bury cable connectors and be careful not to nick the in-
ner cable insulation and thus exposing bare copper conductors.
3. Do not direct bury. Make sure that the DataNodesand DataValvesare installed
in well drained valve boxes and are not subject to flooding or prolonged emersion
in water.
Note: Australian Standards for Lightning protection to be effective is 10 Ohms or less re-
sistance to earth.