The external remote
function is enabled, but
there is no signal to
switch on the generator.
Switch off the external
remote control (see
menu 6300), or switch
the generator to local
mode (see menu 1100),
remote mode (see menu
1200) or send a signal to
the external remote HV
on/off input.
The generator is faulty. Send the generator for
repair, see section 10.
Display is on
Communication is
working
No checking via the
bus
Generator is operating
in local or remote mode.
Enable the fieldbus
mode (see menu 1300).
Setpoint cannot be
set in ‘local mode’
The generator is locked. Unlock the generator
(see section 6.8 and
menu 6110).
Generator is faulty. Send the generator for
repair, see section 10.
Limit LED lights up
Generator is
operating in VC or
AdvOutC mode
Generator is
overloaded
Sparking or short circuit
in connected equipment
Check connected
equipment.
Emitter point in contact
with earth
Prevent the emitter point
from making contact
with earth.
Generator overloaded Reduce output voltage
or increase distance
between the charging
bar/electrode and
material.
Limit LED lights up
Generator is
operating in CC or
AdvCC mode
Maximum set voltage
reached
Increase the maximum
voltage or lower the
maximum current.
Emitter point in contact
with earth
Prevent the emitter point
from making contact
with earth.
Generator overloaded Reduce output current
or increase distance
between the charging
bar/electrode and
material.
External remote input
is not responding
Connection problems Connect the wiring
correctly, see section
5.7.
No signal to the remote
input
Control the input with
the correct signal, see
section 5.7.
External remote mode
not enabled
Enable external remote
for the active operating
mode (see section 6.12,
menu 6310, 6320 and
6330).