3.3.2 Setting parameters
Set the parameters as shown in the table to ensure that the con-
troller recognises the system.
System identification.
Setting mode = INSTALLER
(refer to section on parameter setting levels)
Setting mode = MANUFACTURER
(Refer to section on parameter setting levels)
3.3.3 Checking for correct recognition
To check that the controller has correctly recognised the type of
system on the basis of the parameters entered, display the installer
parameter in row 53.
System n. 2 should appear.
3.3.4 Minimum return thermostat
The thermostat on the return is not supplied with the probe kit. It ser-
ves to activate the by-pass pump if the return temperature is low. It
should be set to 35° C.
NOTE: Once parameters have been set, the unit’s led will be
off during regular operation, and will flash when not required by
the room thermostat. This is NOT a fault signal.
3.4 SYSTEM I2: HEATING WITH
EXTERNAL HOT WATER TANK
The features of this type of system are summed up below:
– Automatic Summer/Winter switchover
– Climate control with outdoor probe
– Boiler works only on demand from room thermostat
– Minimum boiler temperature is maintained
– System pump works only on demand from the room thermostat
– Weekly heating programming
– External hot water tank settings entered directly from RVA43.222
controller
– Hot water is turned on/off using a pushbutton on the controller
– Weekly hot water scheduling
The components included in the boiler kit to be purchased are as follows
(the outdoor temperature probe QAC31 and the boiler probe AQZ21
are sold separately):
SC
A6
MD
MB
M
DB
B9
B10/70/4
B3
B2
H1
TA*
SE
F1
Q1
Q3/y3
L
N
N
L
ALBATROS RVA43.222
PI
E1
K5
F5
K4
F4
Verso comandi accensione
I° e II° stadio bruciatore
vedere schema elettrico caldaia
*Qualora non vi sia un termostato ambiente,
predisporre un ponte permanente
Il collegamento elettrico va eseguito
all'interno del pannello comandi della caldaia.
Per i dettagli consultare lo schema
elettrico della caldaia
TM
PBY
L
N
Per le pompe vedere i morsetti di appoggio in caldaia
Wiring diagram
LEGEND
TA Room thermostat
SC Boiler delivery probe (QAZ21)
SE Outdoor temperature probe
(QAC31)
PI Boiler pump
PBY Bypass pump
TM Minimum return thermostat
Par Description Default values Setup
90 Minimum limitation of boiler temperature 8
4400
91* Type of burner 1
00
140 LPB device address 1
00
170 Input H1 0
11
173 Operating action of contact H1 1
00
* For single stage boilers only
Par Description Default values Setup
9 Operating mode of boiler 2 1
Par Description Value
53 Display of plant type 2
Code Description Quantity
RVA43.222 Control unit 1
QAZ21 (immersion) Boiler delivery probe/boiler probe 1
Wiring must be performed inside the boiler’s
control panel. For details please refer to the boi-
ler’s wiring diagram.
* If there is no room thermostat, set up a per-
manent jumper.
For pumps, refer to supporting terminals on the boiler
Toward burner stage 1 and 2 igni-
tion commands. Refer to boiler
wiring diagram.