APPENDIX 4: COMMISIONING CHECKLIST
Test Nr Task Test to be performed Checklist
DL2 – 1
DL2 – 2
DL2 - 3
Wire and check the
system
Wire together the JB70 LAN and
CU-M001 Graphic display
• Display does not show ‘NO
COMMUNICATION’
Set up the cong as per instruc-
tions
Wire NMEA IN, NMEA OUT
• MFD shows VBW,x.x,y.y,A,x
.x,y.y,A,,A,z.z,A , MTW, VLW
Wire Relay output J2 to common
alarm
• Remove power (AC and
DC) and check you see alarm
DL2 – 4
DL2 – 5
DL2 – 6
Install and connect
sensor for DL2 to the
JB70 unit (J3)
Connect JB70 to CU-
M001 display
Check Sensor
Check Using the service software
and the self test in Cong – Diag-
nostic – Self test,
• Serial Number of sensor
(DL2) should be same as on cable
• Firmware version should be
correct (3.00 or greater)
• Live data should show qual-
ity factor (QF) 8 or 9
Upgrade rmware to the version on
the skipper websites
DL2 – 9
DL2 - 10
Install setup in the
Bridge Conning sys-
tem
Check on MFD that you see inputs
from DL2
• You can see input VBW,
VLW, MTW, occasional VDALR,
Check on MFD that you can see
the Outputs to the Log
• You can see VTG, DPT,
GGA, occasional ACK
DL2 – 11
DL2-12
Check NMEA 1/2 input
Check on display – Cong – Com-
munication, that the input is show-
ing GYRO and GPS information.
• Can see HDT/THS, ROT,
VTG,GGA/GLL
• Can see aft speed on page
D