Parameter List Overview SMA Solar Technology AG
168 SI2012_2224-TEN082311 Technical Description
222 02 AptTmBoost min 120 Absorption time at normal charge
120 = VRLA
90 = FLA
300 = NiCd
depending on the setting in QCG
222 03 AptTmFul h 5 Absorption time at full charge
5 = VRLA
5 = FLA
7 = NiCd
depending on the setting in QCG
222 04 AptTmEqu h 10 Absorption time at equalizing charge
10 = VRL A
10 = FLA
10 = NiCd
depending on the setting in QCG
222 05 CycTmFul d 14 Full charge cycle time
222 06 CycTmEqu d 180 Cycle time at equalizing charge
222 07 ChrgVtgBoost V 2.4 Setpoint of cell voltage at normal charge
2.4 = VRLA
2.55 = FLA
1.65 = NiCd
depending on the setting in QCG
222 08 ChrgVtgFul V 2.4 Setpoint of cell voltage at full charge
2.4 = VRLA
2.5 = FLA
1.65 = NiCd
depending on the setting in QCG
222 09 ChrgVtgEqu V 2.4 Setpoint of cell voltage at equalizing
charge
2.4 = VRLA
2.5 = FLA
1.65 = NiCd
depending on the setting in QCG
222 10 ChrgVtgFlo V 2.25 Setpoint of cell voltage at floating charge
2.25 = VRLA
2.25 = FLA
1.55 = NiCd
depending on the setting in QCG
222 11 BatTmpCps mV/degC 4.0 Battery temperature compensation
4.0 = VRLA
4.0 = FLA
0.0 = NiCd
depending on the setting in QCG
Menu
nr.
Parame
ter.Nr.
Parameter Name Range/Unit Default
value