SMA Solar Technology AG Parameter List Overview
Technical Description SI2012_2224-TEN082311 169
230# Set External
222 12 AutoEquChrgEna Disable
Enable
Enable activates automatic equalization charge
223# Bat Protection
223 01 BatPro1TmStr hhmmss 220000 time for starting battery preservation mode
level 1
223 02 BatPro1TmStp hhmmss 060000 time for stopping battery preservation
mode level 1
223 03 BatPro2TmStr hhmmss 170000 time for starting battery preservation mode
level 2
223 04 BatPro2TmStp hhmmss 090000 time for stopping battery preservation
mode level 2
223 05 BatPro1Soc % 20 SOC limit for preservation mode level 1
223 06 BatPro2Soc % 15 SOC limit for preservation mode level 2
223 07 BatPro3Soc % 10 SOC limit for preservation mode level 3
224# Bat Silentmode
224 01 SilentEna Disable
Enable
Disable Enable Silent mode on the grid
224 02 SilentTmFlo
(Stby)
h 3 max. time for float charge until change to
silent
224 03 SilentTmMax
(Stby)
h 12 max. time for silent mode until transfer into
float
225# Battery Current Sensor
225 01 BatCurSnsTyp - None
60mV
50mV
Current sensor type (60mV, 50mV)
225 02 BatCurGain60 A/60mV 3 external battery current sensor 60mV type
225 03 BatCurGain50 A/50mV 12 external battery current sensor 50mV type
225 04 BatCurAutoCal Start Automatic calibration of the external
battery current sensor
Menu
nr.
Parame
ter.Nr.
Parameter Name Range/Unit Default
value
Description
231# Ext General
231 02 PvFeedTmStr hhmmss 040000 start of PV feed-in
231 03 PvFeedTmStp hhmmss 220000 stop of PV feed-in
231 04 ExtLkTm min 20 Locking time after Reverse Power and/or
relay protection
Menu
nr.
Parame
ter.Nr.
Parameter Name Range/Unit Default
value
Description