Parameter List Overview SMA Solar Technology AG
170 SI2012_2224-TEN082311 Technical Description
231 09 ExtSrc Grid Grid Grid Operation
232# Grid Control
232 01 GdVtgMin V 189 Minimum grid voltage
232 02 GdVtgMax V 259.5 Maximum grid voltage
232 03 GdCurNom A 16 Nominal grid current
232 04 GdFrqNom Hz 50 Nominal frequency
232 05 GdFrqMin Hz 47.65 Minimum grid frequency
232 06 GdFrqMax Hz 50.15 Maximum grid frequency
232 07 GdVldTm sec 30 minimum time required for grid (voltage
and frequency) to be within permissible
range for connection
232 08 GdMod GridCharge
GridFeed
GridCharge Grid interface
232 09 GdRvPwr W 100 permissible grid reverse power
(effective power)
232 10 GdRvTm sec 5 permissible time for grid reverse power
232 15 GdAISns Low,
Medium
standard
High
standard AI sensitivity
233# Gen Control
233 01 GnVtgMin V 17 2. 5 Min. generator voltage
233 02 GnVtgMax V 264.5 Max. generator voltage
233 03 GnCurNom A 25 Nominal generator current
233 04 GnFrqNom Hz 50 Nominal generator frequency (at
nominal load)
230V_50HZ = 50
220V_60HZ = 60
depending on the setting in QCG
233 05 GnFrqMin Hz 44.64 Minimum generator frequency
230V_50HZ = 44.64
220V_60HZ = 50
depending on the setting in QCG
233 06 GnFrqMax Hz 60 Maximum generator frequency
230V_50HZ = 60
220V_60HZ = 70
depending on the setting in QCG
Menu
nr.
Parame
ter.Nr.
Parameter Name Range/Unit Default
value
Description

Table of Contents