SMA Solar Technology AG Parameter List Overview
Technical Description SI2012_2224-TEN082311 171
233 07 GnStrMod Manual
Automatic
start
GenMan
Automatic
start
Generator interface
233 08 GnOpTmMin min 15 Minimum generator operating time
233 09 GnStpTmMin min 15 Minimum generator stop time
233 10 GnCoolTm min 5 Cooling time for Generator
233 11 GnErrStpTm h 6 Generator stop time in case of generator
failure
233 12 GnWarmTm sec 60 warm up time (minimum time required
for generator voltage and frequency to
be within permissible range for
connection)
233 13 GnRvPwr W 100 allowable generator reverse power
(active power)
233 14 GnRvTm sec 30 allowable time for reverse power/
reverse current
233 15 GnCtlMod Cur
CurFrq
Cur External (Gen/Grid) control
(Current or frequency)
233 20 GnAISns Low,
Medium
standard
High
standard AI sensitivity
234# Gen Start
234 01 GnAutoEna Off
On
On activate generator autostart
234 02 GnAutoStr 3 Number of automatic starts
234 03 GnSocTm1Str % 40 SOC limit for switching on generator for
time 1
234 04 GnSocTm1Stp % 80 SOC limit for switching off generator for
time 1
234 05 GnSocTm2Str % 40 SOC limit for switching on generator for
time 2
234 06 GnSocTm2Stp % 80 SOC limit for switching off generator for
time 2
234 07 GnTm1Str hhmmss 0 time 1 for generator request
(begin time 1, end time 2) (hhmmss)
234 08 GnTm2Str hhmmss 0 time 2 for generator request
(begin time 2, end time 1) (hhmmss)
234 09 GnPwrEna Off
On
Off activate generator request as a result of
power
Menu
nr.
Parame
ter.Nr.
Parameter Name Range/Unit Default
value
Description