Parameter Lists SMA Technologie AG
Page 128 SI5048-11:EE4206 Technical Description
#140 Generator Meters
#150 Grid Meters
Menu
no.
Para-
meter
no.
Parameter name Range/
Short descr.
Description
#140 01 GnDmdSrc
None
Bat
Lod
Tim
Run1h
Start
Source for generator request:
= no request
= battery charge state dependent
= load dependent
= time-controlled
= for 1 hour
= manually started
#140 02 GnStt
Off
Idle
Warm
Connect
Run
Retry
Disconnect
Cool
Lock
Fail
FailLock
Generator state:
= switched off
= waiting for request (ready)
= warming up
= connecting
= operation
= restarting
= disconnecting
= cooling down
= locked after operation
= error
= locked after error
#140 03 GnRmgTm hhmmss remaining generator run time (minimum run
time)
#140 04 GnRnStt Off, On state of generator return signal on master
(Dig-In)
Menu
no.
Para-
meter
no.
Name Range/
Short descr.
Description
#150 01 GdRmgTm hhmmss remaining time of GdValTm parameter (valid
grid time)
The "#160 Compact Meters" menu is described in detail in section 10.4
"Compact Meters" (Page 70).