SMA Technologie AG Parameter Lists
Technical Description SI5048-11:EE4206 Page 129
18.2 Adjustable System Parameters
#210 Inverter Settings
#220 Battery Settings
Parameters marked with (Stby) are to be changed only when the Sunny Island
5048 is in standby mode. Once the "ENTER" key is pressed, operating data
values can immediately change to their new settings. Incorrect values in these
parameters can probably not be corrected quickly enough to avoid potential
damage to your system.
All menu items that can only be changed after entering the installer password are
shaded in gray in the following tables.
All parameters can be set using a connected PC/laptop with the Sunny Data
Control software, a Sunny WebBox or a Sunny Boy Control (see section 6.5
"Interface for External Communication" (Page 51)).
Menu
no.
Para-
meter
no.
Parameter name Range/
Short
descr.
Value Description
#210 01 InvVtgNom V 230 nominal inverter voltage
230 = 230V_50HZ
220 = 220V_60HZ
depending on the setting in QCG
#210 02 InvChrgCurMax A 22 maximum AC charging current
#210 03 InvFrqNom Hz 50 nominal inverter frequency
50 = 230V_50HZ
60 = 220V_60HZ
depending on the setting in QCG
Menu
no.
Para-
meter
no.
Parameter name Range/
Short
descr.
Default
value
Description
#221 Battery Property
#221 01 BatTyp
VRLA
FLA
NiCd
VRLA Battery type:
= valve regulated lead acid
= flooded lead acid
= nickel cadmium
can only be changed in QCG
#221 02 BatCpyNom Ah 100 nominal battery capacity (C10)
can only be changed in QCG
#221 03 BatVtgNom V 48 nominal battery voltage
48 = VRLA
48 = FLA
45.6 = NiCd
can only be changed in QCG
#221 04 BatTmpMax degC 40 maximum battery temperature