What to do if the display of my SMA Sunny Island Inverter is dark?
If the display of your Sunny Island is dark, first check if the DC circuit breaker on the Sunny Island is set to "On." The device might have switched off to protect the batteries from deep discharge. Also, the external battery fuse may have tripped.
Why does my SMA Sunny Island connect to the running generator only for a short time?
Your Sunny Island might connect to the running generator for only a short time if the limits for the maximum permissible AC voltage or the minimum permissible frequency of the generator are too strict. These parameters are located in the menu "233# Generator Control". Adjust the voltage and/or frequency limiting values, while being mindful of the technical data for your generator.
Why is my SMA Sunny Island staying on even though I switched the DC circuit breaker to Off?
Your Sunny Island may still be powered by the AC side. To resolve this, switch off all AC consumers and disconnect them from the Sunny Island.
What to do with changing between wintertime and summertime operation on SMA Sunny Island 5048 Inverter?
Save two different parameter sets on the SD card and activate them via the '550.02 ParaLod' parameter.
Why is my SMA Sunny Island 5048 multicluster system not supplying full power output?
If your multicluster system isn't supplying full power output, it could be because an extension cluster's slave has failed. The system continues to operate, but with correspondingly lower output.
What to do if my SMA Inverter battery is discharging even though the generator is running?
If the generator is running but the battery is still discharging, it could be because the power produced by the generator isn't reaching the Sunny Island. Check the voltage and frequency values. Alternatively, the consumer power might exceed the generator power, so check for any error messages to identify the cause.
Why is my SMA Inverter not connecting to the running generator?
There could be several reasons why your Sunny Island isn't connecting to the generator. First, check the generator fuse. If that's fine, see if the power allowed to be fed back into the generator during the permissible time has been exceeded. If it has, set the '540.02 GnAck' parameter to Ackn. If the generator control relay (GnReq) is open, ensure the generator is set to autostart, if required. Also, if a GenMan is used, check the return signal (DigIn) as the generator can only be started using GenMan.
Why does the generator or grid not reconnect, although the cutoff limit (for voltage or frequency) is now no longer being breached on my SMA Sunny Island 5048 Inverter?
The Sunny Island connects with a hysteresis, meaning the connection value is slightly below or above the disconnection value. These limiting values are predefined.
What is required if the SMA Sunny Island is continuously switched off after Low Battery Mode (LBM) when restarting the device?
If the Sunny Island is continuously switched off after Low Battery Mode (LBM) when restarting the device, start the generator manually, if required (e.g.: Run1h). Also, consider the time for warming up: 5 minutes without charging current in BatProtMode can cause the device to change to standby mode.
Output Voltage | 230 V |
---|---|
Nominal AC Voltage | 230 V |
AC Frequency | 50 / 60 Hz |
DC voltage range | 40 - 60 V |
Battery Voltage | 48 V |
Efficiency | 95 % (typical) |
Weight | 40 kg |
Protection class | IP 21 |
Maximum AC Output Power | 5000 W |
Maximum Efficiency | 96 % |
Dimensions (H x W x D) | 550 x 450 x 230 mm |
Operating temperature range | -25 °C to +60 °C |