8.2 Starting the Quick Configuration Guide (QCG)
The QCG is automatically activated during the initial start-up of the Sunny Island. In this case begin
with point 3. If the QCG is not activated automatically, begin with point 1.
1. Switch the Sunny Island DC circuit breaker to the "ON" position.
The Sunny Island initiates the start-up phase. The
notifications shown here are displayed. The last
notification is displayed as soon as the start-up
phase is completed.
2. Press and hold down <ENTER> until the Sunny Island beeps three times.
The QCG is started.
"Start System" (if you have accidentally accessed the QCG and would only like to restart
the system)
"New System" (if you would like to start a new system or perform changes to the plant
configuration)
Error occurrence
If the device displays an error message unexpectedly, this error must be fixed before the
Sunny Island can be put into operation. For this purpose, refer to section
20”Troubleshooting” (page194).
Default setting of parameters
Upon starting the Quick Configuration Guide, viable parameter values are set by default.
Systems with several Sunny Island
If you have a system with more than one Sunny Island, you must first run the QCG on the
slave(s) before starting the master device (display message "INIT MASTER OK START?").
Only the device type is set there. Only start the master device thereafter!
SIBFSBOOT V1.004