SMA Solar Technology AG Operation
Technical Description SI5048-TB-TEN110340 71
The Sunny Island displays a corresponding message for parameters that can only be changed in
standby mode or require a different password level.
10.3 Direct Access - Direct Access to the Parameters
The "600# Direct Access" menu gives you direct access to the selected parameter using the
parameter name or number.
Via the Select Name sub-menu, you have direct access to the following functions:
GnManStr: manual starting of the generator (see section 14.1.4”Manual Generator
Operation” (page112)).
ManChrgSel: manual starting of equalization charge (see section 13.4.3”Equalization
Charge” (page102)).
Via the Select Number menu, you have direct access to every parameter by entering the parameter
number.
Display Description
Incorrect password level, you cannot make any
changes in the menus. This is explained in section
10.5”Entering the Installer Password” (page76).
All menu items and parameters that can only be
changed by the installer are shown with a gray
background in the parameter list (see section
19”Parameter lists” (page146)).
This parameter can only be changed in standby
mode. Stop the Sunny Island to change the parameter
(see section 9.2”Stopping the Sunny Island
(Standby)” (page63)).
Example
Using the menu 600#, you can select the "222.01 BatChrgCurMax" parameter, for
example, to set the maximum battery charging current.
The direct access must be entered as a five-digit number, for example, 22201. Here, the
first three digits describe the menu number and the last two describe the parameter number.
Exit the menu level after the parameter has been set.