EasyManua.ls Logo

SMA Sunny Island 5048 - Failure Categories

SMA Sunny Island 5048
224 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SMA Solar Technology AG Troubleshooting
Technical Description SI5048-TB-TEN110340 201
20.7 Failure Categories
The Sunny Island distinguishes between 5 different levels of failures, each requiring different user
interaction.
Level Description Display on
the
Sunny Island
Meaning
1 Warning Warning Warning, device continues to run. There is an explicit
information on the Home Screen that a warning was
recorded.
2 Malfunction 1 Malfunction Failure that can only be detected during operation.
Device switches off. Device can be restarted
immediately (autostart).
3 Malfunction 2 Malfunction Failure that can also be detected in standby mode.
Device switches off. The device can only be restarted
(autostart) once the system detects that the failure has
ended.
4 Failure Failure Device fault. Device switches off. User interaction
required (failure removal, confirmation, manual
restart).
5 Device defect Defect Device is defect. Device switches off and does not
switch on again. Permanent disable. Device must be
replaced.

Table of Contents

Other manuals for SMA Sunny Island 5048

Related product manuals