Electrical Connection SMA Solar Technology AG
34 SI5048-TB-TEN110340 Technical Description
6.2.3 Cable Protection
In addition to the internal DC circuit breaker, install a separate, external fuse as close as possible to
the battery. Install a suitable fuse link for the fuse according to the maximum specified DC currents
(e.g. NH1 with 250 A).
6.2.4 Connection
There is a "DC —" and a "DC +" terminal provided for each tube terminal lug (max. 70 mm²) for the
battery feed cables in the Sunny Island.
DANGER!
Risk of lethal electric shock. Death or serious burns.
If no external cable protection is available, observe the following:
Lay the DC cables so that they are ground-fault and short-circuit-proof.
If there are short-circuit currents of over 10000 A, use an additional thermal fuse.
DANGER!
Danger to life due to high voltages. Death or serious burns.
Connect the external fuse and the battery cable to the battery only after all
installation work has been completed.