Parameter lists SMA Solar Technology AG
162 SI5048-TB-TEN110340 Technical Description
19.2.3 External Settings (230#)
231# Ext General
232# Grid Control
Number Name Description Value Explanation Default
Value
01 PvFeedTmStr Start time for PV grid
feeding-in
04:00:00
02 PvFeedTmStp Stop time for PV grid
feeding-in
22:00:00
03 ExtLkTm Lock time after reverse
power or relay
protection
0 min 60
min
20 min
05 ExtSrc Generator and grid
operating mode
PvOnly PV only PvOnly
Gen Generator
Grid Grid
GenGrid Generator / Grid
12 ChpEna Enable CHP Disable Disable Disable
Enable Enable
Number Name Description Value Explanation Default
Value
01 GdVtgMin Minimum grid voltage 230 V / 50 Hz 184.00 V
220 V / 60 Hz 194.00 V
02 GdVtgMax Maximum grid
voltage
230 V / 50 Hz 264.50 V
220 V / 60 Hz 242.00 V
03 GdCurNom Nominal power line
current
16.00 A
04 GdFrqNom Nominal power line
frequency
230 V / 50 Hz 50.00 Hz
220 V / 60 Hz 60.00 Hz
05 GdFrqMin Minimum power line
frequency
230 V / 50 Hz 47.50 Hz
220 V / 60 Hz 59.30 Hz
06 GdFrqMax Maximum power line
frequency
230 V / 50 Hz 50.20 Hz
220 V / 60 Hz 60.50 Hz
07 GdVldTm Minimum time
required for grid
(voltage and
frequency) to be
within permissible
range for connection
230 V / 50 Hz 30 sec
220 V / 60 Hz 300 sec