SMA Solar Technology AG Parameter lists
Technical Description SI5048-TB-TEN110340 163
08 GdMod Grid interface GridCharge Charging on
the grid
GridCharge
GridFeed Charging and
feedback on
the grid
09 GdRvPwr Permissible grid
reverse power
(active power)
0 W ...
5000 W
100 W
10 GdRvTm Permissible time for
grid reverse power
0 sec ...
60 sec
5 sec
15 GdAlSns AI sensitivity Low Low Normal
Medium Medium
Normal Normal
High High
37 GdVtgIncProEna Voltage increase
protection
Disable Disable Disable
Enable Enable
38 GdVtgIncPro Boundary for voltage
increase protection
230 V / 50 Hz 253 V
220 V / 60 Hz 242 V
40 Country Installation country
The installation
country is set based
on the corresponding
applicable standard.
The default value is
based on your order.
GER_VDE01
26_1_1
Germany
AS4777 Australia
Other Others
41 GdSocEna Activate the grid
request based on
SOC
Disable Disable Disable
Enable Enable
42 GdPwrEna Activate the grid
request based on
power
Disable Disable Disable
Enable Enable
Number Name Description Value Explanation Default