SMA Solar Technology AG Technical Data
Technical Description SI5048-TB-TEN110340 217
22 Technical Data
Output values SI 5048
Nominal AC voltage (adjustable) UAC, nom 230 V (202 V ... 253 V)
Nominal frequency f
nom
45 ... 65 Hz
Continuous AC output at 25 °C P
nom
5000 W
Continuous AC output at 45 °C P
nom
4000 W
AC output power for 30 min at 25 °C P
30 min
6500 W
AC output power for 1 min at 25 °C P
1 min
8400 W
AC output power for 3 seconds at 25 °C P
3 sec
12000 W
nominal AC current I
AC, nom
21 A
Maximum current (peak value) for 60 ms I
AC, max
120 A
Harmonic distortion of output voltage K
VAC
< 3 %
Power factor cosφ –1 ... +1
Input data
Input voltage (adjustable) U
AC, ext
230 V (172.5 V ... 264.5 V)
Input frequency (adjustable) f
ext
50 Hz ( 40 Hz ... 70 Hz)
Maximum AC input current (adjustable) I
AC, ext
56 A (0 A ... 56 A)
Maximum input voltage P
AC, ext
12.8 kW
Battery Data
Battery voltage (range) U
Bat, nom
48 V (41 V ... 63 V)
Maximum battery charging current I
Bat, max
120 A
Continuous charging current I
Bat, nom
100 A
Battery capacity C
Bat
100 Ah ... 10000 Ah
Charge control IUoU procedure with automatic
full and equalization charge
Battery type VRLA / FLA / NiCd
Efficiency / Power consumption SI 5048
Maximum efficiency 95 % (at 1000 W)
Efficiency > 90 % 5 ... 120 % Pnom