SMA Technologie AG Parameter Lists
Technical Description SI5048-11:EE4206 Page 141
18.4 Functions in Operation
#410 Operation Inverter
#420 Operation Battery
Menu
no.
Para-
meter
no.
Parameter name Range/
Short
descr.
Default
value
Description
#410 01 InvRs
(Stby)
Restart --- triggers inverter reset
#410 02 ParaSto
Set1
Set2
--- Saves parameter settings:
= file 1
= file 2
#410 03 InvTmOpEna Disable
Enable
Disable activates time-controlled inverter
operation
#410 04 InvTmOpStrDt yyyymmdd 20060101 start date of time-controlled inverter
operation
#410 05 InvTmOpStrTm hhmmss 0 start time of time-controlled inverter
operation
#410 06 InvTmOpRnDur hhmmss 0 run time for time-controlled inverter
operation
#410 07 InvTmOpCyc Single
Daily
Weekly
Single repeated cycle time for timer 1
#410 08 ParaLod
(Stby)
Set1
Set2
Factory
--- Loads parameter settings:
= file 1
= file 2
= factory settings
#410 09 CntRs Inv
Bat
Gn
Gd
All
--- clears selected energy meter
Menu
no.
Para-
meter
no.
Name Range/
Short
descr.
Default Description
#420 01 ManChrgSel Idle
Start
Stop
Idle triggers equalization charge
(manual)