SMA Technologie AG The Sunny Island 5048
Technical Description SI5048-11:EE4206 Page 21
2.8 Type Plate/Firmware Version
You can identify the Sunny Island 5048 by the type plate and the firmware version.
• The type plate is located on the left side of the housing.
• You can read the the firmware version of your device on the display using the
"#331.02 FwVer" parameter (see section 18.3 "Diagnostics" (Page 138)).
A Maximum DC voltage Nominal AC voltage I
B DC voltage range AC voltage range K
C Nominal DC output voltage Nominal frequency L
D DC charging voltage range Frequency range M
E Maximum DC operating current Maximum continuous AC current N
F Temperature range Maximum AC input current O
G Protection class Maximum leakage current P
H Manufacturing date Maximum output power Q
.de
Maximum system
voltage
63V=*
Sunny
Island
www.
SMA Technologie AG
Hannoversche Straße1-5
34266 Niestetal, Germany
Hotline : +49 (0)561 - 9522 - 399
Utility Interactive Battery Inverter
DC
Type
SI5048
Nominal output
voltage
230 V *
~
AC
Range of operating
voltage
41...63V =*
DC
Operating voltage
range
202...253V *
~
AC
Nominal output
voltage
48V=*
DC
Nominal output
Frequency
50 Hz*
AC
Charging output voltage
operation range
41...63V =*
DC
Operating frequency
range
45...65 Hz*
AC
Maximum operating
current
200 A =
DC
Maximum continuous
output current
21,7 A
~
AC
Operating temperature range
-25...+50 °C
Maximum input current
(pass thru)
56 A
~
AC
Degree of protection
IP40
Maximum output
fault current
100 A
~
AC
Manufactured
3Q/2006
Maximum
output power
continuous
5000 W/25°C
4000 W/45°C
AC
* Value adjustable For more detailed data refer to
installation & operating instruction
Serial Number
125600XXXX
P1
A
B
C
D
E
F
G
H
I
K
L
M
N
O
P
Q