SMA Solar Technology AG 6 Electrical Connection
Installation Manual SI80H-60H-OffGrid-IA-en-11 39
9. Strip the insulation from the DC– cable and mount a terminal lug.
10. Lead the DC– cable through the cable gland for DC– into the off-grid inverter.
11. Install the DC– cable in the cable channel for DC–
cables. Look for the designation in the cable
channel.
12. Fasten the DC– cable to the DC– terminal using an M8x20 screw and an Allen key (AF 6)
(torque: 4 Nm ... 5.7 Nm).
13. Tighten the swivel nuts of the cable glands.
6.7 Installing Protective Devices for DC Sources
If you install DC sources, you must install the following protective devices:
If the applicable local standards and directives require a fuse-switch-disconnector, install a
fuse-switch-disconnector in the DC sub-distribution.
If a fuse-switch-disconnector is installed, dimension fuse links based on the maximum output
current of the DC sources.
Protect every DC source with a separate miniature circuit-breaker.
8.
Damage to the off-grid inverter due to reverse polarity
Install the DC+ cable in the cable channel
for DC+ cables. Look for the + designation in
the cable channel.
Fasten the DC+ cable to the DC+ terminal using an M8x20 screw and an Allen key
(AF 6) (torque: 4 Nm ... 5.7 Nm).