7 Commissioning SMA Solar Technology AG
96 SI80H-60H-OffGrid-IA-en-11 Installation Manual
• Select the 242.08 Lod2SocTm1Stp parameter and set it to the upper SOC limiting value
for the second level of load shedding.
5. Setting the SOC limiting value for the second interval:
• Select the 242.03 Lod1SocTm2Str parameter and set it to the lower SOC limiting value
for the first level of load shedding.
• Select the 242.04 Lod1SocTm2Stp parameter and set it to the upper SOC limiting value
for the first level of load shedding.
• Select the 242.09 Lod2SocTm2Str parameter and set it to the lower SOC limiting value
for the second level of load shedding.
• Select the 242.10 Lod2SocTm2Stp parameter and set it to the upper SOC limiting value
for the second level of load shedding.
6. Ensure that the multi-function relay used for controlling the first level of load shedding is set to
AutoLod1Soc (see Section 7.10.2).
7. Ensure that the multi-function relay used for controlling the second level of load shedding is set
to AutoLod2Soc (see Section 7.10.2).
7.10.7 Setting Time Control for External Processes
If you wish to control external processes with time control, set the multi-function relay as follows:
1. Switch to installer mode (see Section 7.5).
2. To set timer 1, set the start date, start time, duration and repetition cycle:
• Select the 243.01 RlyTmr1StrDt parameter and set it to the desired start date.
• Select the 243.02 RlyTmr1StrTm parameter and set it to the desired start time.
• Select the 243.03 RlyTmr1Dur parameter and set it to the desired duration.
• Select the 243.04 RlyTmr1Cyc parameter and set it to the desired repetition cycle.
• Ensure that the multi-function relay used for control is set to Tm1 (see Section 7.10.2).
3. To set timer 2, set the start date, start time, duration and repetition cycle:
• Select the 243.05 RlyTmr2StrDt parameter and set it to the desired start date.
• Select the 243.06 RlyTmr2StrTm parameter and set it to the desired start time.
• Select the 243.07 RlyTmr2Dur parameter and set it to the desired duration.
• Select the 243.08 RlyTmr2Cyc parameter and set it to the desired repetition cycle.
• Ensure that the multi-function relay used for control is set to Tm2 (see Section 7.10.2).