7 Commissioning SMA Solar Technology AG
90 SI80H-60H-OffGrid-IA-en-11 Installation Manual
Requirement:
The Sunny Remote Control must be connected to the master of the main cluster.
1. Switch to installer mode (see Section 7.5).
2. Select the 242.01 Lod1SocTm1Str parameter and set it to the lower SOC limiting value.
3. Select the 242.02 Lod1SocTm1Stp parameter and set it to the upper SOC limiting value. The
upper SOC limiting value must be at least 10 percent greater than the lower SOC limiting value.
4. Set the 242.05 Lod1Tm1Str and 242.06 Lod1Tm2Str parameters to the same value,
e.g. both to 000000. This switches time-dependent load shedding off.
7.10 Configuration of the Multi-Function Relays
7.10.1 Use of the Multi-Function Relays
Note the function of the multi-function relays in the following table during the electrical connection.
Multi-function relay Value Function/output
Relay 1 of the off-grid inverter/master,
parameter 241.01 Rly1Op
Relay 2 of the off-grid inverter/master,
parameter 241.02 Rly2Op
Relay 1 of slave 1,
parameter 244.01 Rly1OpSlv1
Relay 2 of slave 1,
parameter 244.02 Rly2OpSlv1
Relay 1 of slave 2,
parameter 245.01 Rly1OpSlv2
Relay 2 of slave 2,
parameter 244.01 Rly2OpSlv2