16 Technical Data
SMA Solar Technology AG
Operating manualSTP110-60-BE-en-16104
MPP Voltage Range for rated power 500V to 800V
Rated input voltage 585V
Minimum input voltage 200V
Initial input voltage 250V
Maximum usable input current per input with an
input voltage < 600V
22 A
Maximum usable input current per input with an
input voltage > 600V
26 A
Maximum short-circuit current per input
2)
40 A
Maximum reverse current into the PV array
3)
0A
Number of independent MPP inputs 12
Strings per MPP input 2
Overvoltage category as per IEC 62109-1 II
16.3 AC Output
Rated power at nominal AC voltage, 50Hz 110000W
Maximum apparent power at cosφ=1 110000VA
Rated apparent power at cosφ=1 110000VA
Nominal grid voltage 400V
Rated grid voltage 400V
Voltage range
4)
320V to 460V
Rated current at nominal grid voltage 158.8 A
Maximum output current 158.8A
Maximum residual output current 420 A
Duration of the maximum residual output current 1 ms
Total harmonic distortion < 3%
Inrush current <10% of the nominal AC current for a
maximum of 10ms
Rated grid frequency 50Hz
Grid frequency
4)
50 Hz / 60 Hz
Operating range at grid frequency 50Hz 45Hz to 55Hz
2)
In accordance with IEC62109-2: I
SCPV
3)
The topology prevents a reverse current from the inverter in the system
4)
Depending on the configured country data set