16 Technical Data
SMA Solar Technology AG
Operating manualSTP110-60-BE-en-16104
MPP Voltage Range for rated power 500V to 800V
Rated input voltage 585V
Minimum input voltage 200V
Initial input voltage 250V
Maximum usable input current per input with an
input voltage < 600V
22 A
Maximum usable input current per input with an
input voltage > 600V
26 A
Maximum short-circuit current per input
2)
40 A
Maximum reverse current into the PV array
3)
0A
Number of independent MPP inputs 12
Strings per MPP input 2
Overvoltage category as per IEC 62109-1 II
16.3 AC Output
Rated power at nominal AC voltage, 50Hz 110000W
Maximum apparent power at cosφ=1 110000VA
Rated apparent power at cosφ=1 110000VA
Nominal grid voltage 400V
Rated grid voltage 400V
Voltage range
4)
320V to 460V
Rated current at nominal grid voltage 158.8 A
Maximum output current 158.8A
Maximum residual output current 420 A
Duration of the maximum residual output current 1 ms
Total harmonic distortion < 3%
Inrush current <10% of the nominal AC current for a
maximum of 10ms
Rated grid frequency 50Hz
Grid frequency
4)
50 Hz / 60 Hz
Operating range at grid frequency 50Hz 45Hz to 55Hz
2)
In accordance with IEC62109-2: I
SCPV
3)
The topology prevents a reverse current from the inverter in the system
4)
Depending on the configured country data set