10 Operation
SMA Solar Technology AG
Operating manual STP110-60-BE-en-16 63
You are logged in on the user interface as Service provider (see Section10.2.2, page57).
Procedure:
In the parameter group Extended Model 2-1 RW select the parameter AFCIActivationEn
and set it to On.
Also see:
Arc-Fault Circuit Interrupter (AFCI)⇒page23
10.11 Resetting the arc-fault circuit interrupter (AFCI)
The basic procedure for changing operating parameters is explained in another section (see
Section10.6, page61).
After 5 detections per day the inverter must be reconnected manually via the user interface of the
inverter.
Requirements:
Your inverter is equipped with AFCI. The type label of your inverter indicates whether your
inverter has AFCI.
You are logged in on the user interface as Service provider (see Section10.2.2, page57).
Procedure:
In the parameter group Extended Model 2-1 RW select the parameter Clear
AFCIAlarmEn and set it to On.
Also see:
Arc-Fault Circuit Interrupter (AFCI)⇒page23
10.12 Configuring the ModbusFunction
Measures for data security during activated Modbus interface
If you activate the Modbus interface, there is a risk that unauthorized users may access and
manipulate the data or devices in your PV system.
To ensure data security, take appropriate protective measures such as:
Set up a firewall.
Close unnecessary network ports.
Only enable remote access via VPN tunnel.
Do not set up port forwarding at the communication port in use.
Requirements:
You are logged in on the user interface as Installer (see Section10.2.1, page56).