6 Mounting
SMA Solar Technology AG
Operating manual STP110-60-BE-en-16 25
6 Mounting
6.1 Installing the AC Sealing Plate (optional)
An optional AC sealing plate with 4 cable glands can be used for the product. The optional AC
sealing plate can be ordered in the SMA online shop (www.sma-onlineshop.com) by indicating the
material number 201013-00.01.
Procedure:
1. Loosen the 4 screws of the AC sealing plate
attached to the inverter at delivery (TX30) and
remove the AC sealing plate.
2. Ensure that the AC device opening is free of contamination.
3. Ensure that the seal of the optional AC sealing plate is undamaged and free of contamination.
4. Attach the optional AC sealing plate to the inverter
using the 4 screws supplied (TX30, torque: 4.3Nm).
6.2 Requirements for the Mounting Location
WARNING
Danger to life due to fire or explosion
Despite careful construction, electrical devices can cause fires. This can result in death or serious
injury.
• Do not mount the product in areas containing highly flammable materials or gases.
• Do not mount the product in potentially explosive atmospheres.
☐ Do not mount the inverter in living areas.
☐ Specialists must have exclusive access to the mounting location.