12 Event messages
SMA Solar Technology AG
Operating manual STP110-60-BE-en-16 87
12.2.59 Event 225 (Sunny Portal: 3416)
Event message:
PV[#] abnormal
Corrective measures:
Check if the -nth PV string must be connected. If not, ignore the event. If so, check the
connection state and ensure that there is a reliable connection.
Ensure that the -nth DC fuse is not damaged.
If the fault cannot be rectified using the indicated corrective measures, contact Service.
12.2.60 Event 226 (Sunny Portal: 3417)
Event message:
PV[#] abnormal
Corrective measures:
Check if the -nth PV string must be connected. If not, ignore the event. If so, check the
connection state and ensure that there is a reliable connection.
Ensure that the -nth DC fuse is not damaged.
If the fault cannot be rectified using the indicated corrective measures, contact Service.
12.2.61 Event 227 (Sunny Portal: 3418)
Event message:
PV[#] abnormal
Corrective measures:
Check if the -nth PV string must be connected. If not, ignore the event. If so, check the
connection state and ensure that there is a reliable connection.
Ensure that the -nth DC fuse is not damaged.
If the fault cannot be rectified using the indicated corrective measures, contact Service.
12.2.62 Event 448, 449 (Sunny Portal: 4013)
Event message:
String [#] reverse polarity