Chapter 5 Display and setting of various functions
HRS-R Series 5.16 Alarm customize function
5-43
Changing of Contact input signal 1 detection Setting and checking
24. Press the [SEL] key once.
The set screen of the changing of contact input signal 1 detection is displayed on the
digital display.
25. Select the changing of contact input signal 1 detection from the table below with [▲]
key or [▼] key, and confirm by pressing “SEL”.
Table 5.16-14 List of set value
Set value
Explanation
Initial value
(Default setting)
This alarm signal is not detected.
Operation continues when this alarm signal is
generated.
Operation is stopped when this alarm signal is
generated.
Changing of Contact input signal 2 detection Setting and checking
26. Press the [SEL] key once.
The set screen of the changing of contact input signal 2 detection is displayed on the
digital display.
27. Select the changing of contact input signal 2 detection from the table below with [▲]
key or [▼] key, and confirm by pressing “SEL”.
Table 5.16-15 List of set value
Set value
Explanation
Initial value
(Default setting)
This alarm signal is not detected.
Operation continues when this alarm signal is
generated.
Operation is stopped when this alarm signal is
generated.
PV
SV
PV
SV

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks HRS018-A 20 R Series and is the answer not in the manual?

SMC Networks HRS018-A 20 R Series Specifications

General IconGeneral
BrandSMC Networks
ModelHRS018-A 20 R Series
CategoryChiller
LanguageEnglish

Related product manuals