HRX-OM-W058
Chapter 5 Display and setting of various functions
5.19 Communication function HRS-R Series
5-62
38. Select contact input signal 2 from the table below with [▲] key or [▼] key, and confirm
by pressing “SEL”.
Table 5.19-20 List of set value
Set value
Explanation
Initial value
(Default setting)
Without input signal
Input of run/stop signal
External switch signal input(N.O. type)
External switch signal input (N.C. type)
Remote signal
*7
*7When the setting of the serial protocol is “Simplified communication protocol 2”, “Remote
signal” cannot be set.
Contact input signal 2 type Setting and checking
39. Press the [SEL] key once.
The set screen of contact input signal 2 type is displayed on the digital display.
40. Select contact input signal 2 type from the table below with [▲] key or [▼] key, and
confirm by pressing “SEL”.
Table 5.19-21 List of set value
Set value
Explanation
Initial value
(Default setting)
Setting/checking are not available if the
setting of contact input signal 1 is OFF.
Alternate signal
Momentary signal
*8
*8 Can be set when the setting of contact input signal 2 is "Run/Stop signal input" or "Remote signal"
Contact input signal 2 delay timer of reading Setting and checking
41. Press the [SEL] key once.
The set screen of contact input signal 2 delay timer of reading is displayed on the digital
display.
PV
SV
PV
SV