HRX-OM-W058
Chapter 5 Display and setting of various functions
HRS-R Series 5.19 Communication function
42. Select contact input signal 2 delay timer of reading from the table below with [▲] key or
[▼] key, and confirm by pressing “SEL”.
Table 5.19-22 List of set value
Initial value
(Default setting)
Setting and checking are not available unless
contact input singal 2 is external switch signal
input (N.O. type or N.C. type).
Setting of contact input signal 2 delay timer of
reading.
Set range is 0 to 300 sec.
Contact input signal 2 OFF detection timer Setting and checking
43. Press the [SEL] key once.
The set screen of contact input signal 2 OFF detection timer is displayed on the digital
display.
44. Select contact input signal 2 OFF detection timer from the table below with [▲] key or
[▼] key, and confirm by pressing “SEL”.
Table 5.19-23 List of set value
Initial value
(Default setting)
Setting and checking are not available unless
contact input singal 2 is external switch signal
input (N.O. type or N.C. type).
Setting of contact input signal 2 OFF
detection timer
Set range is 0 to 10sec.
Contact output signal 1 function Setting and checking
45. Press the [SEL] key once.
The set screen of contact output signal 1 function is displayed on the digital display.