○Error indication
This function is to display error location and content when a problem or an error occurs.
Error Name Error Display Error Type Troubleshooting Method
Over current
Error
The switch output load current is more than
80 mA.
Turn the power off and remove the
cause of the over current.
Then turn the power on.
Residual
Pressure Error
During zero clear operation, pressure
above ±10% of the span between
atmospheric pressure and upper limit of
rated pressure has been applied. After 1
second, the mode will return to
measurement mode. The zero clear range
can vary ±1 digit with individual product
differences.
Perform zero clear operation again
after restoring the applied pressure
to an atmospheric pressure
condition.
Pressurizing
Error
Pressure has exceeded the upper limit of
the set pressure range.
Reset applied pressure to a level
within the set pressure range.
Pressure has exceeded the lower limit of
the set pressure range.
Auto-shift Error
The measured pressure at auto-shift input
exceeded the set pressure range.
∗: After 1 second, measurement mode will return
automatically.
Auto-shift input signal is invalid.
Check the connected equipment
and correct the signal.
System Error
Displayed in the case of an internal data
error.
Turn the power off and turn it on
again.
If resetting fails, an investigation by
SMC Corporation will be required.
If the error can not be reset after the above measures are taken, then please contact SMC.