-82-
No.PF※※-OMY0005
Product individual parameters
Index
Sub
index
Access
1
Parameter
Data
type
2
Initial
value
Data
storage
3
Set value
4
Remarks
dec
hex
1000
0x03E8
0
R/W
Flow Unit
(Selection of display unit)
U8
0
Y
0: L/min (L)
1: cfm (ft
3
)
When the unit selection function is not
included, a read/write to an
un-selectable item is rejected.
1010
0x03F2
0
R/W
CoL
(Selection of display colour)
U8
2
Y
0: rEd (Constantly red)
1: Grn (Constantly green)
2: 1SoG
(OUT1 turns green at ON)
3: 1Sor
(OUT1 turns red at ON)
4: 2SoG
(OUT2 turns green at ON)
5: 2Sor
(OUT2 turns red at ON)
Setting of display colour
1020
0x03FC
0
R/W
N or P
(Switch NPN/PNP)
U8
1
Y
0: nPn
1: PnP
Setting the switch output
1070
0x042E
0
R/W
Reference condition
U8
0
Y
0: std
(Standard condition)
1: nor
(Normal condition)
1080
0x0438
0
R/W
Temperature Unit
(Selection of temperature
display unit)
U8
0
Y
0: C
1: F
When the unit selection function is not
included, a read/write to an
un-selectable item is rejected.
1090
0x0442
0
R/W
Pressure Unit
(Selection of pressure
display unit)
U8
0
Y
0: MPa
1: kPa
2: kgf/cm
2
3: bar
4: psi
When the unit selection function is not
included, a read/write to an
un-selectable item is rejected.
1200
0x04B0
0
R/W
OUT1 setting
OUT1
(Select the target for
setting)
U8
0
Y
0: FLoW (Flow rate)
1: Temp (Temperature)
2: PrES (Pressure)
3: AC (Accumulated)
4: PLS
(Accumulated pulse)
5: Err (Error output)
6: oFF (Output OFF)
1210
0x04BA
1
R/W
OUT1 setting
(FloW)
ModE1
(Selection of output
mode)
U8
0
Y
0: HYS (Hysteresis)
1: Wind
(Window comparator)
2
R/W
1ot
(Selection of output
type)
U8
0
Y
0: 1_P (Normal output)
1: 1_n (Reverse output)
Setting of OUT1 output normal and
reserved output
1220
0x04C4
1
R/W
P_1 (n_1)
(Selection of output
set value)
S16
2000
Y
Setting range
0x0028 to 0x1068
(40 to 4200)
Setting of OUT1 output set value
(Hysteresis)
2
R/W
H_1
(Setting of OUT1
hysteresis)
U16
200
Y
Setting range
0x0000 to 0x1040
(0 to 4160)
Setting of OUT1 hysteresis
(Hysteresis)
3
R/W
P1L (n1L)
(Lower limit of window
comparator)
S16
1200
Y
Setting range
0x0028 to 0x1068
(40 to 4200)
Setting of OUT1 output set value
(Lower limit of window comparator)
4
R/W
P1H (n1H)
(Upper limit of window
comparator)
S16
2400
Y
Setting range
0x0028 to 0x1068
(40 to 4200)
Setting of OUT1 output set value
(Upper limit of window comparator)
5
R/W
WH1
(Window comparator
hysteresis)
U16
400
Y
Setting range
0x0000 to 0x0820
(0 to 2080)
Setting of OUT1 hysteresis
(Window comparator)
6
R/W
dtH1
(Delay time ON)
U16
0
Y
Setting range
0x0000 to 0x1770
(0 to 6000)
Setting of OUT1 delay time ON
10 ms increments
7
R/W
dtL1
(Delay time OFF)
U16
0
Y
Setting of OUT1 delay time OFF
10 ms increments