DIRIS A40/A41 - RS485 - JBUS/MODBUS
®
50
DIRIS A40/A41 - Ref.: 536 103 B GB
Decimal Hexa. Number Text Unit
address address of words
LIST OF PARAMETERS TO BE DISPLAYED OR PROGRAMMED (FUNCTION 3, 6 OR 16)
3 : 100 kWh/kvarh/kVAh
4 : 1000 kWh/kvarh/kVAh
5 : 10000 kWh/kvarh/kVAh
523 20B 1 OUT 1 impulse duration:
1 : 100 ms
2 : 200 ms
3 : 300 ms
4 : 400 ms
5 : 500 ms
6 : 600 ms
7 : 700 ms
8 : 800 ms
9 : 900 ms
524 20C 1 OUT 2 allocation of the pulse output:
0 : kWh +
1 : kvarh +
2 : kVAh
3 : kWh -
4 : kvarh -
525 20D 1 OUT 2 impulse value:
0 : 0.1 kWh/kvarh/kVAh
1 : 1 kWh/kvarh/kVAh
2 : 10 kWh/kvarh/kVAh
3 : 100 kWh/kvarh/kVAh
4 : 1000 kWh/kvarh/kVAh
5 : 10000 kWh/kvarh/kVAh
526 20E 1 OUT 2 impulse duration :
1 : 100 ms
2 : 200 ms
3 : 300 ms
4 : 400 ms
5 : 500 ms
6 : 600 ms
7 : 700 ms
8 : 800 ms
9 : 900 ms
527 20F 1 Type of analog output OUT 1:
0 : 0/20 mA
1 : 4/20 mA
2 : 30 V
528 210 1 Output allocation analog OUT 1:
0: I1
1 : I2
2 : I3
3 : In
4 : U12
5 : U23
6 : U31
7 : ΣP
8 : ΣQ
9 : ΣS
10 : ΣPFL
11 : V1
12 : V2
COMMUNICATION

Other manuals for socomec DIRIS A40

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the socomec DIRIS A40 and is the answer not in the manual?

socomec DIRIS A40 Specifications

General IconGeneral
TypeMultifunction Meter
DisplayLCD with backlight
Operating Temperature-10 to +55 °C
MountingPanel mounting
Measurement ParametersVoltage, Current, Power, Energy, Frequency
CommunicationRS485, Modbus RTU
Storage Temperature-25°C to +70°C
Protection DegreeIP20
StandardsIEC 61557-12
AccuracyClass 0.5
Dimensions96 x 96 mm