DIRIS A40/A41 - RS485 - JBUS/MODBUS
®
GB
51
DIRIS A40/A41 - Ref.: 536 103 B GB
LIST OF PARAMETERS TO BE DISPLAYED OR PROGRAMMED (FUNCTION 3, 6 OR 16)
Decimal Hexa. Number Text Unit
address address of words
COMMUNICATION
13 : V3
14 : F
15 : ΣPFC
16 : I Sys
17 : U Sys
18 : V Sys
19 : ΣP predicted
20 : ΣQ predicted
21 : ΣS predicted
22 : T°C 1
23 : T°C 2
24 : T°C 3
25 : T°C internal
529 211 1 Value
at 0 or 4 mA from analog output OUT 1
530 212 1 Unit
at 0 or 4 mA from analog output OUT 1
:
0 : /
1 : k
2 : M
531 213 1 Value
at 20 mA from analog output OUT 1
532 214 1 Unit
at 20 mA from analog output OUT 1:
0 : /
1 : k
2 : M
533 215 1 Type of analog output OUT 2 :
0 : 0/20 mA
1 : 4/20 mA
2 : 30 V
534 216 1 Output allocation analog OUT 2:
0 : I1
1 : I2
2 : I3
3 : In
4 : U12
5 : U23
6 : U31
7 : ΣP
8 : ΣQ
9 : ΣS
10 : ΣPFL
11 : V1
12 : V2
13 : V3
14 : F
15 : ΣPFC
16 : I Sys
17 : U Sys
18 : V Sys
19 : ΣP predicted
20 : ΣQ predicted
21 : ΣS predicted
22 : T°C 1
23 : T°C 2
24 : T°C 3
25 : T°C internal
535 217 1 Value
at 0 or 4 mA from analog output OUT 2