DIRIS A40/A41 - RS485 - JBUS/MODBUS
®
GB
87
DIRIS A40/A41 - Ref.: 536 103 B GB
COMMUNICATION
Decimal Hexa. Number Text Unit
address address of words
3654 E46 1 Query! : maximum phase-to-phase value :
0 : no
5: U12
6: U23
7: U31
3655 E47 2 Value
3657 E49 1 Query! : maximum phase-to-neutral value :
0 : no
22 : V1
23 : V2
24 : V3
3658 E4A 2 Value
3660 E4C 2 Duration ms
3662 E4E 1 Day
3663 E4F 1 Month
3664 E50 1 Year
3665 E51 1 Hour
3666 E52 1 Minute
3667 E53 1 Second
Decimal Hexa. Number Text Unit
address address of words
3668 E54 1 Query! : maximum phase-to-phase value :
0 : no
5: U12
6: U23
7: U31
3669 E55 2 Value
3671 E57 1 Query! : maximum phase-to-neutral value :
0 : no
22 : V1
23 : V2
24 : V3
3672 E58 2 Value
3674 E5A 2 Duration ms
3676 E5C 1 Day
3677 E5D 1 Month
3678 E5E 1 Year
3679 E5F 1 Hour
3680 E60 1 Minute
3681 E61 1 Second
LAST 10 TEMPORARY VOLTAGE SURGE EVENT LOG (FUNCTION 3)
Voltage surge n-6
Voltage surge n-7