DIRIS A40/A41 - RS485 - JBUS/MODBUS
®
88
DIRIS A40/A41 - Ref.: 536 103 B GB
COMMUNICATION
Decimal Hexa. Number Text Unit
address address of words
3682 E62 1 Query! : maximum phase-to-phase value :
0 : no
5: U12
6: U23
7: U31
3683 E63 2 Value
3685 E65 1 Query! : maximum phase-to-neutral value :
0 : no
22 : V1
23 : V2
24 : V3
3686 E66 2 Value
3688 E68 2 Duration ms
3690 E6A 1 Day
3691 E6B 1 Month
3692 E6C 1 Year
3693 E6D 1 Hour
3694 E6E 1 Minute
3695 E6F 1 Second
Decimal Hexa. Number Text Unit
address address of words
3696 E70 1 Query! : maximum phase-to-phase value :
0 : no
5: U12
6: U23
7: U31
3697 E71 2 Value
3699 E73 1 Query! : maximum phase-to-neutral value :
0 : no
22 : V1
23 : V2
24 : V3
3700 E74 2 Value
3702 E76 2 Duration ms
3704 E78 1 Day
3705 E79 1 Month
3706 E7A 1 Year
3707 E7B 1 Hour
3708 E7C 1 Minute
3709 E7D 1 Second
LAST 10 TEMPORARY VOLTAGE SURGE EVENT LOG (FUNCTION 3)
Voltage surge n-8
Voltage surge n-9