Three Phase Inverters with Synergy Technology PN: SExxK-xxxxIxxxx
102 Appendix F: Immunity Standards
Appendix F: Immunity Standards
The information in this appendix complies with the IEEE 1547-2018 standard. The IEEE
1547-2018 standard, establishes criteria and requirements for interconnection of
distributed energy resources (DER) with electric power systems (EPS) and associated
interfaces.
Test type Test method Test Level
Radiated Immunity IEEE C37.90.2 20 V/m
EFT IEEE C37.90.1, C62.45, C62.41.2
+3 kV
+4 kV
Surge IEEE C62.45, C62.41.2, UL 1741
+3 kV
+6 kV
Oscillatory Test IEEE C37.90.1 2.5 kV