SE3680H SE4000H SE5000H SE6000H Unit
INSTALLATION SPECIFICATIONS
AC output -
Supported Cable
Diameter
9 - 16 mm
AC - Supported Wire
Cross Section
1 - 13 mm
2
Dimensions (HxWxD) 450 x 370 x 174 mm
DC input
(1)
1 x MC4
pair
2 x MC4 pairs
Weight with
Connection Unit
10 11.4 11.9 kg
Noise < 25 dBA
Cooling Natural Convection
Operating
Temperature Range
(2)
,
-40 to +60 °C
Ambient air pressure minimum 860hPa - 1060hPa
Protection Rating
IP65 - Outdoor and Indoor (Inverter with
Connection Unit)
Recommended OCPD size per grid:
Inverter
Maximum Output
Current (A)
Minimum Fuse Rating (A)
Maximum fuse rating
(A)
SE3680H 16 20 50
SE4000H 18.5 25 50
SE5000H 23 32 50
SE6000H 27.5 40 50
Inverter
Maximum output
current (A)
Minimum fuse Rating (A)
Maximum fuse rating
(A)
SE4K 6.5 10 33
SE5K 8 10 33
SE27.6K 40 50 63
(1)
Connection of additional strings in parallel to a single input is allowed as long as the cumulative current
does not exceed 45A.
(2)
Full power up to at least 50°C. For power de-rating information refer to:
https://www.solaredge.com/sites/default/files/se-temperature-derating-note.pdf
Technical Specifications - EV Charging Single Phase Inverter (Europe & APAC)
83
EV Charging Single Phase Inverter Guide MAN-01-00583-1.5