E: Export limit
P: Production limit
I: Minimum import
Dis: Disabled - no limit
Energy Control: The method by which to manage the energy.
Storage Control: Enables reserving a minimum battery charge level.
Advanced: For enabling external production
3.
Select Energy Ctrl.. The following is displayed, showing the SolarEdge applications:
M a x S e l f - c o n s u m e
T i m e o f U s e
B a c k u p O n l y
D i s a b l e
Max Self-consume (MSC): Maximize Self-consumption
Time of Use (TOU): Charge/Discharge Profile Programming
Backup Only: Supply power to loads during power outage
Disable: No energy control, that is, the battery is not used
Setting Backup-Only
When the inverter is set to Backup-only mode, the battery will discharge to supply
power to the backed-up loads only upon power outage.
To set up Backup-only:
1. Access the Energy Ctrl menu as described above.
2.
Select Backup only. The Energy Manager screen changes to display the following:
L i m i t C o n t r o l < D i s >
E n e r g y C t r l < B U >
S t o r a g e C o n t r o l
Setting MSC + Backup Power
In this mode, you first set the system to maximize self-consumption (MSC), and then
the level of stored energy to be reserved for backup.
To set up MSC + Backup Power:
1. Access the Energy Ctrl. menu as described above.
2.
For maximizing self consumption, select Max Self-Consume. The Energy Manager
screen changes to display the following:
StorEdge Solution with Backup MAN-01-00262-1.5
116Configuring StorEdge Applications